Heaty Complete Fix Series
The Heaty Complete Fix series enables the standard-compliant replenishment of larger heating and cooling systems. It is available in various sizes, with 6 to 46 litres of mixed-bed resin, and offers a range of filling capacities and system capacities. The GLT version also features an interface for building management systems.
Heaty Complete Fix
Art.-Nr. 100345 to 100348
Make-up unit with BA system separator for larger heating and cooling systems with LED measuring cell. The Heaty Complete Fix is available with different mixed bed resin quantities: Mini (6 l), Small (9.5 l), Big (23 l) and Tall (46 l). They also differ in terms of maximum filling capacity and capacity.
Your advantages
- LED measuring cell for resin change
- Controlled make-up for sustainable heating and cooling water quality
- Compliance with VDI 2035, ÖNORM H 5195-1 and SWKI BT 102-1
- Easy handling
- Safety thanks to indicator resin as a consumption indicator
Included
- Water meter for documenting the volume of make-up water
- Filling combination BA with pressure reducer if no system separator is available on site
- LED measuring cell indicates when the conditioning resin needs to be replaced
Heaty Complete GLT
Art.-Nr. 100380 to 100383
Make-up unit with BA system separator for larger heating and cooling systems incl. Connection to the building management system. The Heaty Complete GLT is available with different mixed bed resin quantities: Mini (6 l), Small (9.5 l), Big (23 l) and Tall (46 l). They also differ in terms of maximum filling capacity and capacity.
Your advantages
- Connection to building management system
- Controlled make-up for sustainable heating and cooling water quality
- Compliance with VDI 2035, ÖNORM H 5195-1 and SWKI BT 102-1
- Easy handling
- Safety thanks to indicator resin as a consumption indicator
Included
- Water meter for documenting the volume of make-up water
- Filling combination BA with pressure reducer if no system separator is available on site
- Automatic switch-off when the limit value is reached
- Probe measurement for even more safety
- BMS connection for connection to the building management system
Heaty Complete Fix Series: Top-ups for larger systems
The units in the Heaty Complete Fix series enable larger heating and cooling systems to be reliably replenished in accordance with standards. Both unit variants (Fix and GLT) are fitted with a BA system separator and an LED measuring cell, and are available with mixed-bed resin volumes of 6, 9.5, 23 or 46 litres. The maximum filling capacity and total capacity vary depending on the size selected. The GLT version also features an interface for building management systems, thereby enabling integration into higher-level monitoring and control systems.
Heaven7 - UWS Cloud Portal
A new approach to digital system monitoring.
The UWS Cloud Portal brings together system information, measurement logs and system messages on a single central platform for the first time.
All data from the WaterBoy App is automatically documented in accordance with standards and can be accessed at any time. At the same time, intelligent Heaven7 devices such as the Racun series or replenishment solutions such as the Heaty Complete PROfessional deliver important information directly to the cloud – for example, in the event of leaks or when Vadion pH-Control mixed-bed resin has been used up.
This creates digital documentation of system statuses and operating data – clear, structured and available at any time.
measure – treat – replenish – document
One platform. All information. Maximum transparency.
Technical data
| Heaty Complete Fix | Heaty Complete GLT | |
| Integration with building management systems | - | Yes |
| Max. Filling capacityg | 360 to 2.400 l/h | |
| Capacity at 420 μS/cm at < 100 μS/cm | 900 to 6840 l | |
| Mixed bed contents | 6 to 46 l | |
| Weight (approx.) | 8,3 to 37,4 kg | |
| Power supply | 230 V – 50 Hz | |