Stationary heating water treatment
Heaty Racun 300 Advanced Plus
Stationary heating water treatment
Heaty Racun 300 Advanced Plus
Art.-Nr. 100481-SL
- Continuous monitoring of conductivity and make-up water quantity
- Automatic treatment and shut-off
- Recording of operating data on SD memory card
- Connection to the building management system
- Integrated magnetic flux filter
- Fine filter
- Differential pressure measurement
- Adjustable volume flow
- Stainless steel centrifugal pump
- Leakage protection
- Modbus
Interested? Contact us in writing or give us a call on +49 9869 91910-0.
Make an appointment
- Ideal for system sizes from 60 to 500 m³
- Improved system water quality in existing systems using the bypass process
- Suitable for initial treatment and backfeeding
- Operable control computer with touchscreen
- CAN bus for communication with CAN bus devices
- Modbus-TCP (optional)
- Recording of operating data and control via internet (optional)
- Timer and wake-up function
- BMS connection
- Recording of operating data on SD memory card
- Flow control of the total volume from 1.8 m³/h
up to 7.2 m³/h - Electronic flowmeter
- Differential pressure cut-off if the filter is dirty and the minimum volume flow is not reached
Max. filling capacity | 3,000 l/h |
Ø circulation capacity in bypass process | Adjustable from 1,800 to 7,200 l/h |
Max. operating pressure | 6 bar |
Max. operating temperature | 80°C |
Fine filter | 1 µ |
Weight (including mixed bed resin filling) | approx. 143 kg |
Mixed bed content | 63 l |
Capacity at 420 μS/cm to < 100 | 9,360 l |
Power supply | 230 V / 50/60 Hz |
Suitable for hot water up to 80°C | ✓ |
Bypassable | ✓ |