Stationary heating water treatment

Heaty Racun 300 Advanced Plus

Stationary heating water treatment

Heaty Racun 300 Advanced Plus

Art.-Nr. 100481-SL
  • Continuous monitoring of conductivity and make-up water quantity
  • Automatic treatment and shut-off
  • Recording of operating data on SD memory card
  • Connection to the building management system
  • Integrated magnetic flux filter
  • Fine filter
  • Differential pressure measurement
  • Adjustable volume flow
  • Stainless steel centrifugal pump
  • Leakage protection
  • Modbus
Interested? Contact us in writing or give us a call on +49 9869 91910-0.
Make an appointment
Your advantages
Technical data
Included in delivery
Downloads (coming soon)
  • Ideal for system sizes from 60 to 500 m³
  • Improved system water quality in existing systems using the bypass process
  • Suitable for initial treatment and backfeeding
  • Operable control computer with touchscreen
  • CAN bus for communication with CAN bus devices
  • Modbus-TCP (optional)
  • Recording of operating data and control via internet (optional)
  • Timer and wake-up function
  • BMS connection
  • Recording of operating data on SD memory card
  • Flow control of the total volume from 1.8 m³/h
    up to 7.2 m³/h
  • Electronic flowmeter
  • Differential pressure cut-off if the filter is dirty and the minimum volume flow is not reached
Max. filling capacity 3,000 l/h
Ø circulation capacity in bypass process Adjustable from 1,800 to 7,200 l/h
Max. operating pressure 6 bar
Max. operating temperature 80°C
Fine filter 1 µ

 

Weight (including mixed bed resin filling)  approx. 143 kg
Mixed bed content 63 l
Capacity at 420 μS/cm to < 100 9,360 l
Power supply 230 V / 50/60 Hz
Suitable for hot water up to 80°C
Bypassable

Heaty Racun 300 Advanced Plus

Capacity calculator for reprocessing units

With our capacity calculator you can easily and quickly calculate the filling capacity of your unit as well as the expected required amount of Vadion pH-Control mixed bed resin. Please select whether it is a new or existing unit.
UWS Füllgerät
Mischbetttauscher
°dH des Wassers
Heizwasser in Liter
Füllkapazität Ihres Gerätes:
Füllwasser Kapazität ca.
20.700 l
Benötigte Gesamtmenge Vadion in Liter ca.
0,11 l
Contact