Measuring technology

L-BOXX PST measuring case

Measuring technology

L-BOXX PST measuring case

Art.-Nr. 200001

Measuring case for annual mandatory testing of the system separator. Functions to be tested are tightness, start of opening of the relief valve, tightness of the relief valve, venting of the medium-pressure zone to atmospheric pressure and the tightness of the outlet side

  • High-precision differential pressure gauge with a resolution of 5 mbar for recording the required trigger pressure of > 140 mbar.
  • All-in-one unit with fine control valve for checking the start of opening and closing of the relief valve of the safety fitting.
  • Self-closing quick connectors for connecting the test hoses enable the test to be carried out quickly and easily.
  • Overpressure-safe differential pressure measurement chamber up to 7°bar on the plus and minus side of the unit.
  • Documentation template for the test report as a printed and digital template – available with company imprint on request.
  • Connection parts for testing different manufacturers of safety fittings in standard sizes in self-sealing design available in the test unit.
  • Detailed operating instructions with explanatory notes for the end customer on the necessity of the annual function and maintenance check.

Backflow preventer.

Interested? Contact us in writing or give us a call on +49 9869 91910-0.
Make an appointment
Your advantages
Technical data
DIN EN 1717
Downloads (coming soon)
  • High-precision differential pressure gauge with a resolution of 5 mbar for recording the required trigger pressure of > 140 mbar.
  • All-in-one unit with fine control valve for checking the start of opening and closing of the relief valve of the safety fitting.
  • Self-closing quick connectors for connecting the test hoses enable the test to be carried out quickly and easily.
  • Overpressure-safe differential pressure measurement chamber up to 7°bar on the plus and minus side of the unit.
  • Documentation template for the test report as a printed and digital template – available with company imprint on request.
  • Connection parts for testing different manufacturers of safety fittings in standard sizes in self-sealing design available in the test unit.
  • Detailed operating instructions with explanatory notes for the end customer on the necessity of the annual function and maintenance check.
Feature of the differential pressure gauge
Visual Digital display of differential pressure, selectable in mbar,
PSI, mH20, mmHG and cmH20
RS 232 Available, optional cable and software tool
Automatic shut-off The measuring device has an automatic shut-off function to save battery power (after 10 minutes without input). The function is disabled if the unit shows “Rec.” in the display for continuous measurement
Battery replacement Change the 9 V block battery when the battery symbol LBT appears on the left side of the display.

 

Aluminium case dimensions

Measuring case  350 x 440 x 240 mm
Cardboard packaging YES
Total weight 4.85 kg

The measuring case is a test unit developed by UWS Technologie GmbH, which enables the annual maintenance of the functionality of system separators of the type BA to be carried out quickly, safely and easily, as required by both sets of European standardisation regulations (DIN EN 806 / DIN EN 1717) and the national supplementary standard DIN 1988 Part 100. The test is carried out in accordance with DVGW recommendation twin 02 in order to guarantee the function of these safety fittings at all times.

Capacity calculator for reprocessing units

With our capacity calculator you can easily and quickly calculate the filling capacity of your unit as well as the expected required amount of Vadion pH-Control mixed bed resin. Please select whether it is a new or existing unit.
UWS Füllgerät
Mischbetttauscher
°dH des Wassers
Heizwasser in Liter
Füllkapazität Ihres Gerätes:
Füllwasser Kapazität ca.
20.700 l
Benötigte Gesamtmenge Vadion in Liter ca.
0,11 l